ETR Electrical Testing & repair
Test Frequencies
General Installation
Domestic accommodation – general Domestic accmomdation – rented houses and flats |
– 1 year |
change of occupancy/10 years change of occupancy/5 years |
Residential accommodation (Houses of Multiple Occupation) – halls of residence, nurses accommodation, etc. |
1 year | change of occupancy/5 years |
Educational establishments | 6 months | 5 years |
Industrial | 1 year | 3 years |
Commercial | 1 year | Change of occupancy/5 years |
Offices | 1 year | 5 years |
Shops | 1 year | 5 years |
Laboratories | 1 year | 5 years |
Hospitals & Clinics
Hospitals and medical clinics – general areas Hospitals and medical clinics – medical locations |
1 year 6 months |
5 years 1 year |
Buildings open to the public
Cinemas | 1 year | 1-3 years |
Church installations | 1 year | 5 years |
Leisure complexes (excluding swimming pools) |
1 year | 3 years |
Places of public entertainment | 1 year | 3 years |
Restaurants and hotels | 1 year | 5 years |
Theatres | 1 year | 3 years |
Public houses | 1 year | 5 years |
Village halls/Community centres | 1 year | 5 years |
Special and specfic installations (for medical locations see above)
Agricultural and horticultural | 1 year | 3 years |
Swimming pools | 4 months | 1 year |
Caravans Caravan parks |
1 year 6 months |
3 years 1 year |
Highway power supplies | as convenient | 6-8 years |
Marinas | 4 months | 1 year |
Fish farms | 4 months | 1 year |
Emergency lighting | daily/monthly | 3 years |
Fire alarms | daily/weekly | 1 year |
Launderettes | monthly | 1 year |
Petrol filling stations | 1 year | 1 year |
Construction site installations | 3 months | 3 months |